EU Code of Conduct Best Practices for Data Centres
Posted on 28 March 2025

Himaya Sewwandi
Project Manager
Comes from a background of Environmental Engineering and specialised in Biohydrogen.
Introduction
With data centres becoming the backbone of digital infrastructure, energy efficiency is no longer an option but a necessity. The European Code of Conduct for Energy Efficiency in Data Centres provides a roadmap for operators to enhance sustainability, reduce operational costs, and meet regulatory requirements.
The 2025 Best Practice Guidelines for the EU Code of Conduct on Data Centre Energy Efficiency serves as a key reference for data centre operators looking to enhance energy efficiency. It outlines recognised best practices, providing a standardised framework to ensure clarity in implementing energy-saving measures. The document is valuable not only for operators but also for IT service customers and suppliers, helping them align with environmental and sustainability goals. Additionally, it plays a role in regulatory frameworks, including the Taxonomy Delegated Act for climate mitigation and the 2023 Energy Efficiency Directive.
One critical aspect of energy efficiency is monitoring and reporting. Without accurate data on energy consumption and environmental conditions, making informed decisions to improve efficiency becomes challenging. Section 9 of the Best Practice Guide outlines key strategies for energy measurement, data collection, and reporting with the purpose of helping data centres track, optimise, and enhance their operations.
As per the guide, the essential elements of energy monitoring and reporting for data centre are as follows.
Measuring Energy Use & Environmental Performance
A robust energy monitoring system starts with measuring consumption at various levels. Many data centres still lack separate utility meters, making it difficult to track specific energy usage. Here’s how data centres can improve visibility:
- Total energy consumption monitoring: Installing meters to track the entire energy use of a data centre, including IT systems, cooling, and power distribution, is the first step. This ensures better visibility into total consumption and is essential for reporting under the EU Code of Conduct for Data Centres.
- IT-specific energy monitoring: Beyond overall consumption, measuring the energy delivered directly to IT systems provides crucial insights into efficiency. This can include power from UPS systems and other direct feeds to IT cabinets.Temperature & humidity monitoring: Keeping a close eye on temperature and humidity levels ensures cooling systems are running efficiently and IT equipment isn’t exposed to conditions that could cause overheating or excessive energy waste. Sensors can be installed at room level, within cooling units (CRAC/CRAH), and even at the cabinet or device level.
- Temperature & humidity monitoring: Keeping a close eye on temperature and humidity levels ensures cooling systems are running efficiently and IT equipment isn’t exposed to conditions that could cause overheating or excessive energy waste. Sensors can be installed at room level, within cooling units (CRAC/CRAH), and even at the cabinet or device level.
- Granular power monitoring: Energy consumption varies across different levels of a data centre. Monitoring power at distribution boards, cooling systems, and IT racks allows for better energy optimisation, helping to detect inefficiencies in real time.
- Smart IT equipment selection: Selecting IT hardware based on energy efficiency metrics (such as SERT and SPEC power) ensures that data centres operate with power-efficient servers. Considering real-world workloads, rather than just peak performance per watt, leads to more informed procurement decisions.
Energy Use and Environmental Data Collection & Performance Logging
Accurate measurement and logging of energy use and environmental conditions are crucial for optimising data centre efficiency. Once metering devices are installed, the collected data must be systematically logged and stored to enable performance analysis, identify inefficiencies, and support sustainability goals. The following practices outline different levels of data collection, ranging from manual readings to fully automated logging, providing data centre operators with valuable insights into energy consumption patterns and cooling efficiency.
- Periodic Manual Readings (Entry-Level): Basic energy, temperature, and humidity data should be recorded manually at regular intervals, ideally during peak load times. While manual readings meet the Code of Conduct reporting requirements, automated methods are preferred for better accuracy and efficiency.
- Automated Daily Readings: Replacing manual readings, automated daily data collection allows for more effective energy management by providing consistent and reliable insights.
- Automated Hourly Readings: Enhancing data accuracy, hourly readings enable detailed assessments of IT energy use variations based on workload fluctuations, improving efficiency management.
- Achieved Free Cooling / Economised Cooling Hours: Recording and logging free and economised cooling hours help track reliance on mechanical cooling systems. By understanding the proportion of time spent on mechanical refrigeration versus free cooling, operators can optimise cooling strategies to reduce energy consumption and enhance overall sustainability.
Energy Use and Environmental Performance Reporting
Regular reporting of energy consumption and environmental conditions is essential for managing data centre efficiency and sustainability. By systematically collecting and analysing energy and environmental performance data, operators can make informed decisions to optimise facility operations. The following practices outline various levels of reporting, ranging from basic written reports to fully integrated automated systems.
- Written Reporting: The minimum requirement for energy reporting includes periodic written reports referencing standardised KPIs, such as Power Usage Effectiveness (PUE), IT Equipment Energy Efficiency (ITEEsv), and Water Usage Effectiveness (WUE), following ISO/IEC 30134 and EN 50600-4 standards. This ensures consistency and compliance with industry and regulatory requirements.
- Energy and Environmental Reporting Consoles: Automated monitoring systems provide real-time insights into energy consumption and environmental conditions, enabling facility managers to track efficiency trends and detect anomalies.
- Integrated IT/M&E Energy and Environmental Reporting Consoles: Advanced reporting systems that integrate IT workload data with energy usage metrics, allowing for a holistic approach to energy management and optimisation.
- Achieved Free Cooling / Economised Cooling Hours Reporting: Tracking the proportion of time spent using free cooling versus mechanical refrigeration helps optimise cooling strategies, reducing overall energy consumption.
- PUE, REF, and KPI-Based Reporting: Regular reporting of key performance indicators, including PUE, Renewable Energy Factor (REF), Energy Reuse Factor (ERF), and Carbon Usage Effectiveness (CUE), supports compliance with EU Commission EED reporting requirements and enhances transparency in energy performance.
How RE24 Can Support
At RE24, we recognise that data centres need real-time insights, automated reporting, and precise energy tracking to lead in the green transition. Our platform enables operators to align with the EU Code of Conduct for Energy Efficiency in Data Centres, while streamlining compliance and driving measurable carbon reduction. From procurement to performance analytics, RE24 delivers the tools needed to optimise energy use, reduce Scope 2 emissions, and achieve both sustainability and cost-efficiency at scale.
RE24 Insights – Our real-time energy tracking platform enables automated hourly energy monitoring, helping data centres align with best practices like automated readings, IT workload tracking, and efficiency reporting.
PPA Procurement with RE24 Marketplace – Need to meet renewable energy targets? Our platform helps data centres source hourly-matched renewable energy via Power Purchase Agreements (PPAs), ensuring compliance with carbon reduction goals like CUE (Carbon Usage Effectiveness) and GHGP Scope 2 reporting.
The message is clear: if you can measure it, you can improve it. Investing in real-time monitoring and performance reporting is the key to creating efficient, cost-effective, and sustainable data centres for the future. Visit https://re24.energy/